Air Cooled Packaged Low Temperature Chiller (htlt A)

You are Here: Product / Air Cooled Chiller / Packaged Low Temperature Chiller / Air Cooled Packaged Low Temperature Chiller (HTLT A) / Low Temperature Chiller--air Cooled 3HP To 8HP

Low Temperature Chiller--air Cooled 3HP To 8HP

Low temperature chiller--air cooled 3HP to 8HP
  • Air Cooled Packaged Low Temperature Chiller (HTLT-A)
  • Brand:HERO-TECH
  • Model:HTLT-3A,HTLT-5A,HTLT-6A,HTLT-8A
  • Type:Air-Cooled
  • Certification:CE, UL, Other
  • Cooling Capability(kw):0.6kw to10kw (0C to -35C)
  • Update Time:03/05/2013
Detailed Info
Low temperature chiller--air cooled 3HP to 8HP

Design Features

¨      Original famous brand Semi-hermetic piston compressor adopted, features sufficient cooling capacity, stable performance, and excellent quality.
¨      SCHNEIDER brand electric components ensure the chiller unit running stably with long service time.
¨      Equipped famous brand water pump, with large flow, high efficiency and durability.
¨      Compact design, easy to install and operate, convenient to clean and maintenance.
¨      High efficient shell and tube evaporator adopted, ensuring high cooling efficiency.
¨      Aluminum fin condenser---air cooled type.
Shell and tube evaporator—air cooled type.
¨      R22, R404A refrigerant for option.
¨      380v-415v/50hz 3ph for standard design.  Different design available on request.

Parameter table        
Model HTLT-3A HTLT-5A HTLT-6A HTLT-8A
nominal cooling capacity -10C kw 3.8 6.3 7.5 9.1
-20C 1.9 3 4 6
-30C 1 1.6 1.9 2.7
-35C 0.67 1.04 1.5 2.3
power source   3PH  380V-415V  50HZ
refrigerant type   R22/R404A/R507
control   Thermostatic expansion valve
compressor type   Semi-hermetic piston
power kw 2.25 3.75 4.5 6
condenser type   finned copper tube + low noise outer rotor fan
evaporator type   Shell and tube/plate heat exchanger
inlet and outlet inch 1 1 1 1
dimension length mm 980 1120 1120 1300
width mm 560 610 610 680
height mm 1320 1390 1390 1530
weight kg 135 175 210 310

Remarks:
1. norminal cooling capacity according to:
temperature difference from 3C to 8C;
cooling air inlet 30C, outlet 38C;
2. chiller should be used under 40C ambient temperature;
3. Specification, appearances and dimensions are subject to change without notice.